ELTEC CABLES AND INSTRUMENTS
GST : 24AADFE1261G1ZY

Call us: 08045479549

trusted seller
RTD Extension Wire Ceramic Yarn Insulated

RTD Extension Wire Ceramic Yarn Insulated

Product Details:

  • Product Type RTD CABLES
  • Material SPC WIRE, CERAMIC YARN
  • Usage INDUSTRIAL
  • Click to View more
X

RTD Extension Wire Ceramic Yarn Insulated Price And Quantity

  • 100 Meter

RTD Extension Wire Ceramic Yarn Insulated Product Specifications

  • INDUSTRIAL
  • SPC WIRE, CERAMIC YARN
  • RTD CABLES

RTD Extension Wire Ceramic Yarn Insulated Trade Information

  • Yes
  • Free samples are available
  • 100 Mtrs. COIL WRAPPED IN POLYTHENE 200 to 500 Mtrs. on plastic spool Above 500 Mtrs. on wooden drum
  • Australia North America Middle East Africa Central America South America Asia
  • All India
  • CE & ISO 9001:2015

Product Description

RTD Extension Wire Rx CC

RTD Cables are used as an extension wire to transmit Signal from RTD Sensor to Control Unit. They are available in 2,3,4,6,8,9  cores as per the requirement of RTD SENSOR design for Simplex & Duplex Construction. The main application of these wires is for extreme temperature conditions.

APPLICATIONS

PRODUCT FEATURES

·      RTD Sensors & Extension Wires

         Continuous use up to 800 °C

·     RTD Autoclave

         Single exposure up to 1000°C

      Medical Instruments & Scientific Equipments

        Good Thermal Durability & Strength

       Sensors, Load Cells & Pressure Transducers

         Flame Retardant

       Electronics & Communication Equipment

         Superior Abrasion Resistance

       Process Instrumentation

        Better flexibility


PRODUCT  SPECIFICTIONS:

Conductor

Silver Plated Copper wires sizes from 28 AWG to 20 AWG as per MIL 168780 & JSS 5103492, Refer Table for most popular & standard wire sizes.

Core Insulation

Braided Ceramic Fiber

No. of Cores

2, 4, 6, 8 or even more

Construction

Cores twisted

Outer Sheath

Braided Ceramic Fiber

SS  JACKET

Optional Outside SS Metal braid

Color Coding

Confirms to EN 60751, supplied with color tracers

 FEW STANDARD RTD CABLE WIRE SIZES as per MIL 16878

Sr. No.

Size in AWG

No. of strands/dia. of each strand (mm)

Parameters of conductor (Nominal)
(As per JSS 51034)

Nominal Dia. of Insulated Wire

Dia. (mm)

Cross section (sq. mm)

Resistance Ohm/km at 20oC

Elongation % (Min)

ET
(250 V) AC

E
(600 V ) AC

EE
(1000 V) AC

 

1.

26/7/34

7/0.16

0.48

0.1409

133.7

9.0

0.79

0.99

1.24

 

2.

24/7/32

7/0.2

0.60

0.2270

83.2

9.0

0.91

1.12

1.37

 

3.

24/19/36

19/0.13

0.63

0.2407

80.2

9.0

0.91

1.12

1.37

 

4.

22/7/30

7/0.25

0.75

0.3547

52.5

13.5

1.07

1.27

1.52

 

5.

22/19/34

19/0.16

0.80

0.3820

49.8

9.0

1.07

1.27

1.52

 

6.

20/7/28

7/0.32

0.97

0.5630

33.0

13.5

1.27

1.47

1.73

 

7.

20/19/32

19/0.2

1.00

0.6162

30.3

9.0

1.27

1.47

1.73

 














 